Podtronix C1D1 20 W × 38 D × 10 H - 760 sq ft

Podtronix C1D1 20 W × 38 D × 10 H - 760 sq ft

$99,000 (USD)

Location:Kansas

Description

A factory-engineered Class 1 Division 1 room with 760 square feet of classified working space, complete with gas detection, dry chemical fire suppression and a monitored fire alarm panel. The original PodTronix factory submittal drawing is available and should accompany any listing — it carries the model number, engineered dimensions, full electrical and ventilation specification and the NFPA compliance list.


Model

PodTronix HZ-BIP-SW-201040-8L — factory submittal drawn 6/8/2020

Inside Dimensions

20 ft-0 in W × 38 ft-0 in D × 10 ft-0 in H — 760 sq ft

Outside Dimensions

20 ft-7 7/8 in W × 40 ft-6 3/8 in D × 12 ft-0 in H; floor to fan 13 ft-2 5/8 in

Construction

18 GA steel wall panels, powder coated white, 2 in pre-punched flanges · 18 GA single-wall ceiling · full-wall rear exhaust plenum engineered for maximum air movement at floor and working-surface level · base on floor rails with 1 in drop anchors · man access door, 18 GA steel with explosion vent latches

Ventilation

16 in exhaust + 16 in intake tubeaxial fans (Dayton), 800 CFM base · 1 HP motors mounted outside the airflow · VFD speed control · minimum base airflow 800 CFM, minimum purge 2,400 CFM, keeping exhaust below 25% LEL

Electrical

240 V @ 58.6 A FLA · UL listed control panel with 3-phase VFD · (8) UL listed C1D2 ceiling lights, 120–277 V · all hazardous-location conduit and sealing fittings included

Gas Detection

C1D1 explosion-proof hydrocarbon sensor at each exhaust vent 4 in above floor · RKI Beacon 110 / Sensor Display M2A · photographed live reading 0% LEL with no faults

Fire Suppression

Pyro-Chem dry chemical system · MCH3 control head · manual pull-pin release, pin sealed · three or more agent tanks

Fire Alarm

Fire-Lite MS-2 two-zone control panel, monitored · green AC power, zero trouble LEDs

Compliance

Built to meet or exceed NFPA 1, 30, 33, 70E (2018), 58 (2017), 91 (2015), CAFC, INFC · engineered per job · NFPA 704 Health 2 / Flammability 3 / Instability 0

Inspection History

Fire system inspections passed 2023, 2024, 6/12/2025 and 6/3/2026

Condition

Like new and currently live. Gloss white panels, no dents, no scuffing, no chemical staining on the pod, panels, tanks or devices.

Specifications

ManufacturerPodtronix
ConditionNew
Stock Number00346