HAL Extraction Model 215U C1D1 Booth 10x23x8.5' (Brand New Still in Original Crate)

Location:Seattle, WA
Description
HAL Extraction Model 215U Class I, Division 1, Group D Extraction Booth, 215 Sq Ft
This is a turnkey C1D1 extraction booth from HAL Extraction, built for hydrocarbon and ethanol extraction labs. It has 215 sq ft of interior workspace, enough for a closed-loop extractor, recovery pumps, a chiller and support equipment in one code-compliant room. It’s a modular panel design: 18-gauge powder-coated steel panels meet the NFPA 33 (2018) 5.3.2 construction requirements and bolt together, so the booth can be taken down, moved and set up again.
The booth comes with complete safety and ventilation systems. Two 12" explosion-proof fans run at two speeds. Supply and exhaust plenums are designed to move the most air at floor and work-surface level, where heavier-than-air solvent vapors collect. A UL-listed infrared gas sensor detects butane, propane, ethanol, isopropyl alcohol and CO₂. It automatically raises the booth to purge airflow at 10% of the lower explosive limit (LEL) and triggers audible and visual alarms at 25% LEL. Everything runs from a UL 508A-listed control panel with variable speed drives and a micro PLC, and the whole system runs on a single 20-amp, 208V single-phase circuit.
Dimensions & Construction
- Interior space: 215 sq ft
- Exterior dimensions: 10'0" W × 23'7" L × 8'5" H
- Interior dimensions: 9'9" W × 22'4" L × 8'2" H
- Maximum height with fans: 9'8"
- Panels: (49) 18-gauge powder-coated steel, meeting NFPA 33 (2018) 5.3.2
- Door: 90-minute fire-rated 18-gauge steel, left-hand reverse, with a 7" × 22" window and panic bar
- Anchors: (75) 1" drop anchors, 3 per panel
- Utility penetrations: 2 plates with (2) 3/4", (4) 1-1/8", (8) 1-3/8" and (2) 1-3/4" ports, all with fire-rated hole plugs
Ventilation & Safety
- Fans: (2) 12" explosion-proof fans
- Airflow: 500 CFM base, 1,500 CFM purge, 2 speeds
- Plenums: supply and exhaust, with airflow focused at floor and work-surface level
- Gas sensor: UL-listed infrared, C1D1 explosion-proof; detects butane, propane, ethanol, IPA and CO₂
- Alarm set points: amber light and purge airflow at 10% LEL; amber light, purge airflow and audible alarm at 25% LEL
- Light alarm: amber, rated Class I, Div. 2
- Sound alarm: 24V DC, 109 dB at 1 m
- Lighting: (5) UL-listed 2-tube C1D1 explosion-proof fixtures
Electrical & Controls
- Power: one 20A, 208V single-phase circuit; control panel FLA 14.9A, booth as configured 5.3A
- Control panel: UL 508A listed, with (2) variable speed drives and a micro PLC
- Control settings: Off / Fan On / Fan and Lights On
Installation Notes
- The booth must be at least 3 ft from other operations, or separated by a 1-hour fire-rated wall, partition or floor/ceiling.
- The 3 ft perimeter around the door is a Class I, Division 2 hazardous location.
- Fire suppression, odor mitigation, and setup and assembly are not included.
Specifications
| Manufacturer | HAL |
| Model | 215U |
| Condition | New |
| Stock Number | 00361 |
| Exterior dimensions: | 10'0" W × 23'7" L × 8'5" H |
| Interior dimensions: | 9'9" W × 22'4" L × 8'2" H |
| Maximum height with fans: | 9'8" |
| Fans Airflow: | 500 CFM base, 1,500 CFM purge, 2 speeds |